Print Back
  • Nominal sizes: 7.5 &10 Tons
  • Up to 14.1 IEER / 11.0 EER / 3.4 COP
  • For use with matching RHCYP Models
  • Refrigerant Type: R-454B
RPCY
Unit of Measure
Items RPCY
RPCY2090CAZ
RPCY Commercial Split Classic® Series Heat Pump
RPCY
RPCY2090DAZ
RPCY Commercial Split Classic® Series Heat Pump
RPCY
RPCY2090YAZ
RPCY Commercial Split Classic® Series Heat Pump
RPCY
RPCY2120CAZ
RPCY Commercial Split Classic® Series Heat Pump
RPCY
RPCY2120DAZ
RPCY Commercial Split Classic® Series Heat Pump
Voltage N/A 208 V230 V N/A 460 V N/A 575 V N/A 208 V230 V N/A 460 V
Number of Phases N/A 3
Nominal Capacity N/A 90000 Btu7.5 TR N/A 90000 Btu7.5 TR N/A 90000 Btu7.5 TR N/A 120000 Btu10 TR N/A 120000 Btu10 TR
Total Capacity N/A 85500 Btu/hr N/A 85500 Btu/hr N/A 85500 Btu/hr N/A 114000 Btu/hr N/A 114000 Btu/hr
Net Sensible Capacity N/A 62215 Btu/hr N/A 62215 Btu/hr N/A 62215 Btu/hr N/A 84000 Btu/hr N/A 84000 Btu/hr
Net Latent Capacity N/A 23285 Btu/hr N/A 23285 Btu/hr N/A 23285 Btu/hr N/A 30000 Btu/hr N/A 30000 Btu/hr
EER N/A 11.0
IEER N/A 14.1
Indoor CFM N/A 2875 ft³/min N/A 2875 ft³/min N/A 2795 ft³/min N/A 4050 ft³/min N/A 4050 ft³/min
Compressor Type N/A Z-Scroll
Number of Compressors N/A 1
Compressor - Rated Load Amperes (RLA) N/A 26.3 A N/A 11 A N/A 9.2 A N/A 26.5 A N/A 14 A
Compressor - Locked Rotor Amperes (LRA) N/A 178.5 A N/A 95.3 A N/A 65 A N/A 255 A N/A 123 A
Number of Fans N/A 1 N/A 1 N/A 1 N/A 2 N/A 2
Fan Motor - Full Load Amperes N/A 5.2 A N/A 3 A N/A 1 A N/A 5.2 A N/A 3 A
Minimum Circuit Ampacity N/A 39 A N/A 17 A N/A 13 A N/A 44 A N/A 24 A
Fuse or HACR Circuit Breaker - Minimum N/A 45 A N/A 20 A N/A 15 A N/A 60 A N/A 30 A
Fuse or HACR Circuit Breaker - Maximum N/A 60 A N/A 25 A N/A 20 A N/A 70 A N/A 35 A
Outdoor Coil - Face Area N/A 32.8 ft²
Outdoor Coil - No. Rows N/A 2
Outdoor Coil - CFM N/A 5700 ft³/min N/A 5700 ft³/min N/A 5700 ft³/min N/A 11400 ft³/min N/A 11400 ft³/min
Refrigeration Per Circuit N/A 328.5 oz9939 g N/A 328.5 oz9939 g N/A 328.5 oz N/A 460 oz14189 g N/A 460 oz14189 g
Depth N/A 31 1/8 in N/A 31 1/8 in N/A 31 1/8 in N/A 38 3/8 in N/A 38 3/8 in
Width N/A 42 11/16 in N/A 42 11/16 in N/A 42 11/16 in N/A 73 7/8 in N/A 73 7/8 in
Height N/A 48 13/16 in N/A 48 13/16 in N/A 48 13/16 in N/A 44 3/4 in N/A 44 3/4 in
Weight N/A 428 lb N/A 428 lb N/A 428 lb N/A 642 lb N/A 642 lb
Shipping Weight N/A 448 lb N/A 448 lb N/A 448 lb N/A 662 lb N/A 662 lb
Features N/A
    The RPCY Series commercial split models are engineered for reliable operation and consistent heating and cooling performance. Designed for easy maintenance and serviceability, all access panels can be opened or removed without affecting the structural strength of the unit, helping facilitate easier routine maintenance such as coil cleaning or component inspection. Stamped louvered panels offer 100% protection for the condenser coil, adding to unit performance and reliability.
    Available power options: 208-230V / 3 phase / 60 Hz • 460V / 3 phase / 60 Hz • 575V / 3 phase / 60 Hz
    Limited Warranty (Commercial Applications): Parts – 1 Year • Compressor – 5 Years. Additional extended warranty packages available through ProtectionPlus®.